Safety: CAT III 1000V / CAT IV 600V
Standards: IEC61000-4-30 (2008) S class, EN50160 (2007)
Easy operation to capture the power quality problem
Single-phase 2 W/Single-phase 3 W/ 3-phase 3 W/ 3-phase 4 W
Display: Run Chart, Bar Chart, Vector Graphic, Waveform,Event List, Readings
8G Memory Card to make the long-term measuring data storage
Support USB Interface
Support LAN Interface

Specifications

Measurement Range

Resolution

Accuracy

Voltage/Current/Frequency

Channel

3-phase line input+1neutral line input

Vrms(dc+ac)

1~1000Vrms

0.1Vrms

±5%

Vpk

1~1400Vpk

0.1Vpk

±5%

V(CF)

1.0~>2.8

0.01

±5%

Arms

1~3000A

1A

±1% ± 5digits

1~300A

0.1A

±1% ± 5digits

Apk

1~4000Apk

1A

±1% ± 5digits

A(CF)

1~10

0.01

±5%

Frequency

42.5~57.5Hz(50Hz nominal)

0.01Hz

±0.01%

51~69Hz(60Hz nominal)

0.01Hz

±0.01%

Dips & Swells

Vrms1/2

0~200% of nominal voltage

0.1Vrms

±1%

Arms1/2

1~3000A

1A

±1% ±5 counts

1~300A

0.1A

±1% ±5 counts

Threshold levels

Programmable thresholds in percent of nominal voltage

Event detection based upon ½ cycle rms voltages

Captures Dips,Swells Interruptions and Rapid Voltage Changes

Duration

Hhh, mm, ss, mmm

0.5cycle

1cycle

Harmonic

Harmonic Order

1~50

 

 

Inter-Harmonic Order

1~49

 

 

Voltage

0.0~100.0%

0.10%

±0.1%±nx0.1%

Current

0.0~100.0%

0.10%

±0.1%±nx0.1%

THD

0.0~100.0%

0.10%

±2.5%

DC Relative

0.0~100.0%

0.10%

±2%

Frequency

0~3500Hz

1Hz

1Hz

Phase

-360°~0°

± nx1.5°

Power And Energy

Active Power/Apparent Power/Reactive Power

1.0~20.00MW

0.1kW

±1.5±10counts

Energy

0.00kWh~200GWh

10Wh

±1.5±10counts

Power Factor

0~1

0.01

±0.03

Flicker

Pst(1min),Pst,Plt,PF5

0.00~20.00

0.01

±5%

Unbalance

Voltage

0.0~5.0%

0.10%

±0.5%

Current

0.0~20.0%

0.10%

±1%

Voltage Phase Angle

-360°~0°

±2digits

Current Phase Angle

-360°~0°

±5digits

Voltage Transient

Vpk

±6000Vpk

1V

±15%

Vrms

10~1000Vrms

1V

±2.5%

Min. Tested Time

50us

Sampling Rate

20kS/s

Inrush Current

Arms(AC+DC)

0~3000Arms

0.1

±1%±5digits

Inrush Duration

6s~32 min selectable

10ms

±20ms

Logger

Recording

Parameter,duration time and time interval can be set by user,which can be export on PC

Memory

8G

Max. recording time

1 year

System Monitor

Parameters

Vrms, Arms, Harmonic Volts, THD Volts, Plt, Vrms1/2, Arms1/2, Vneg, Hz, dips and swells, unbalance

Record Time

2h~7days

Record Event Number

>10000

Limits

According EN50160 or customer definable